Pre-discontinuation treatment:
Thoroughly clean the surface of oil and dirt, apply rust preventive oil (recommended Nox-Rust 365 water-based coating).
Run for 30 minutes to repel moisture and upgrade winding insulation resistance to ≥10MΩ.
Storage environment:
Temperature -15℃~40℃, humidity ≤70%, away from corrosive gases.
Vertical motors avoid lying down to prevent bearing deformation.
Test before commissioning:
Shaking table test insulation resistance (≥1MΩ), lower than the standard need to drying treatment.
Manually rotate the rotor to confirm that there is no stagnation.